VAPOUR BARRIER
|
|
| |
Vapour barrier is needed in insulating cold ceilings and damp spaces. The vapour barrier is normally installed above the INFRAHEAT -heaters, but it can also be placed between the covering materials and the heater when the heat flow from the heaters to the covering material needs to be ensured. In addition to plastic, the vapour barrier can be made out of plastic-coated board.
The allowed covering materials in connection with the Infraheat-heating.
|
Cover material
|
Thickness mm |
Element 125 W/m² |
Element 150 W/m² |
|
CHIPBOARD e.g. Leijona, Vibopan (coated)
|
8 10 12 16 |
yes yes yes yes |
yes yes yes yes |
|
BOARDED PANEL e.g. Groove or gap panel
|
8 12 16 22 |
yes yes yes yes |
yes yes yes yes |
|
PLASTERBOAD esim. Cyproc
|
9 11 12 |
yes yes yes |
yes yes yes |
|
WALLBOARDS hard
|
5 06 |
yes yes |
yes yes |
|
WALLBOADS medium hard for example Leijona (juutti)
|
8 10 |
yes yes |
yes yes |
When using other covering materials, one must make sure that the allowed thermal resistance values are not exceeded.
|
Maximum thermal resistance (m² °C/W)
|
125 W/m² |
150 W/m² |
175 W/m² |
| 0,16 |
0,13 |
0,09 |
Thermal resistance m = cover material (m) / thermal conductivity of material (W/m²C)
|
|